A91

A completely unattended startup/shutdown and run controller for engine driven equipment. This user friendly, compact, state-of-the-art microprocessor based controller, covers all basic start stop operations plus other features only found on more sophisticated and expensive controllers.

The A91 is designed to operate from a 12 or 24 volt battery, and requires a magnetic sensor (pickup) for speed detection.

Features:

■ Microprocessor Based Automatic Controller
■ Field Programmable Trip Points
■ Five LED Signal Indicators
■ Startup Lockout Timer
■ Interfaces With Other Existing Murphy Products
■ NEMA 3R “Weatherproof” Enclosure

Contact Us

Please be as specific as possible by including how we can assist along with any relevant information such as spec number, BOM number, or serial number.

ower Input: 12 or 24 VDC nominal (specify).

Standby Power Consumption: <50mA.

Magnetic Pickup Input: Requires 2 V rms minimum.

Sensor Input Polarity: Negative (-).

Outputs: Five (5) open collector transistor 500 mA sink.
Two (2) relay, 5 Amp maximum at 12 or 24 VDC (sourcing).

Reverse Polarity Protection: 200 volt peak reverse voltage.

On-board Memory: 8k PROM (programmable, read only memory); data retention 10 years.

Operating Temperature Range: -20 to 140°F (-25 to 60°C).

Operating Humidity Range: 0-95% Non-Condensing

User Trip point Adjustments: Five (5) on-board potentiometers (320° turn).

Test-Off-Automatic Toggle Switch: Three position switch for:

  • Test: Starts engine in automatic mode and runs until switched “off” or emergency shutdown occurs.
  • Off: Disconnects all power to control circuits, Stop/disables engine from starting and resets shutdown indicators.
  • Auto: Automatic start/stop sequencing is initiated by external switches and signals.

Cycle Crank Timer: 5 crank attempts 7 seconds each; 4 rest periods 15 seconds each, before overcrank.

Overspeed Trip Point Setting: From 2500-9000 Hz.

Crank Disconnect Speed Setting: From 400-2500 Hz.

Shutdown Time Delay: 15 seconds after engine start; locks out low lube oil and high temperature.

Engine Run LED: Turns“on”when crank disconnect occurs.

Shutdown Output: Removes DC output or operates dry relay contacts for engine shutdown (depending on model used).

Start/Stop: SPDT momentary; or SPST maintained switches.

Warmup Time Delay: Field adjustable from 0-300 seconds to load the engine after warmup (model -WC only).

Cooldown Time Delay: Field adjustable from 0-300 seconds (model -WC only).

Enclosure: Weatherproof NEMA 3R.

Enclosure Coating: Red enamel.

Subpanel Coating: White enamel.

Murphy by Enovation Logo

Authorized Distributor

Palmer Johnson is an authorized distributor and service provider for Murphy by Enovation products.

Genuine Parts

Thousands of parts ready to ship in as little as two hours from our store at shop.pjpower.com.

Service and Support

Seven master rebuild centers, ten full-service centers, and an extensive dealer network to serve you.